2026 Florida Energy Code Changes for Homes and Commercial Buildings

Writer: Christian Voelkel
Christian Voelkel
Nov 18
2 min read

The 9th Edition (2026) Florida Building Code, Energy Conservation, is built on the current Florida energy code with changes adopted from the 2024 IECC. Here is what changes for residential and commercial work.

Homes

  • Performance path: the maximum e-Ratio drops from 0.95 to 0.85, roughly 10% more stringent (R405).

  • Duct leakage testing is required on the performance path unless all ducts and air handlers are inside the thermal envelope.

  • Maximum area-weighted SHGC drops from 0.50 to 0.40. The exception for overhangs of 4 feet or more remains.

  • Prescriptive skylights are limited to U-0.60 and SHGC 0.28.

  • New additional efficiency requirement: at least 10 credits from at least two measures in Table R407.2, plus 5 more for homes over 5,000 square feet.

  • Mechanical ventilation flow testing is now mandatory, with a new test report (R403.6.3). Bathroom exhaust needs controls such as timers, occupancy sensors or humidity control.

  • Equipment sizing rules now depend on single-, two- or multi-stage equipment, and latent capacity must meet the calculated latent load.

  • REScheck is no longer an accepted compliance option, and solar-ready zones must be shown on the construction documents.

  • Smart thermostats count toward the programmable thermostat requirement. R-20 air-impermeable insulation is allowed in unvented attics under listed conditions.

Commercial buildings

  • The performance path replaces the fixed 85% threshold with a variable percentage, and on-site renewable credit is capped at 5% of energy cost.

  • Building air leakage tightens from 0.40 to 0.35 cfm/ft² at 75 Pa. Hotels and Group I-1 buildings tested by a third party can use 0.27 cfm/ft² at 50 Pa, and dwelling and sleeping units have testing and reporting requirements.

  • Higher minimum efficiencies for air conditioners, heat pumps, boilers and VRF systems. New controls for large boilers.

  • Demand-controlled kitchen ventilation is required for Type I hood systems over 5,000 cfm.

  • New dehumidification limits, occupied-standby setbacks, lower lighting power allowances and daylight controls for secondary sidelit zones.

  • Data centers follow ASHRAE 90.4, and the list of additional efficiency measures grows to 39.

Source

DBPR 2026 Energy Code Changes Overview (Florida Building Commission). This is a plain-language summary of the Florida Building Commission's published Analysis of Changes, not the code itself. Always check the adopted code text and your local building department before you design or permit. Questions about how a change affects your project? Call Voelkel Engineering at 850-288-0333.

 
 
 