2026 Florida Building Code: Roofing, Windows and Building Envelope Changes
Roofing and the building envelope get some of the most practical changes in the 9th Edition (2026) Florida Building Code. Most of them show up in plan review and inspection, not in design.
Hip and ridge
Asphalt hip and ridge shingles must either be tested to UL 2375 modified to 110 mph, with a label on the package, or be installed with two 1-inch roof cement spots per side under each shingle in addition to fasteners (1507.2.7.2, R905.2.6.2).
Metal hip and ridge covers must be tested for uplift to ANSI/MCA FTS-1 (1504.3.1.1, R905.10.4.1).
Underlayment has to lap at least 6 inches over hips and ridges unless ventilation openings are provided (R905.1.1).
Drip edge and flashing
Drip edge is now required on many more roof types, generally at slopes of 2:12 and steeper, installed over the underlayment and fastened 4 inches on center.
Flashing requirements are added for metal shingles, slate, wood, metal panels, modified bitumen, liquid-applied, and solar roof systems.
Roof coatings get their own section (R909), and asphalt shingle coatings move out of the reroofing rules to 1507.2.10 and R905.2.9.
Reroofing: recover vs. replacement (EB 706.3)
Exception 3 lets a roofer remove only the upper roof covering or system and keep the substrate below, such as insulation or lightweight insulating concrete, if it is adequate for the new roof.
A self-adhering underlayment or vapor barrier already adhered to the deck can stay in place, with a new membrane installed over it.
New sections 706.7.3.1 through 706.7.3.3 list which underlayments can go over existing self-adhering underlayment, including for tile roofs and low-slope roofs.
Windows, doors and walls
Exterior windows and doors need a permanent label, mark or etching that traces back to the manufacturer and product. The temporary label stays on until final approval, and only one design pressure rating is allowed per standard (1709.5.1).
Doors under an overhang can skip water testing only with a Limited Water rating and an overhang ratio of 1 or more, extending past both sides of the door.
LRFD design pressures may be multiplied by 0.6 for garage doors (1709.5.2.1, R609.4).
Soffits under elevated buildings must be designed for ASCE 7 wind pressures (R703.1.2.1).
A prescriptive vinyl siding fastening table is added, limited to 30 psf (R703.11.1).
Lightning protection attachments on roofs must be designed by a registered design professional for wind loads.
Sources
FBC 2026 Significant Changes, Analysis of Changes, Residential, Analysis of Changes, Existing Building (Florida Building Commission), and FRSA's technical articles. This is a plain-language summary of the Florida Building Commission's published Analysis of Changes, not the code itself. Always check the adopted code text and your local building department before you design or permit. Questions about how a change affects your project? Call Voelkel Engineering at 850-288-0333.